The following is a comparison of Canadian versus US code requirements for propane motor fuel installations. This is accurate to the best of our knowledge and is provided only for illustrative purposes. However, we cannot guarantee its accuracy or completeness. Anyone undertaking an alternative fuel conversion MUST obtain the latest regulations in their jurisdiction and follow them both to the letter and to the spirit of the law.

If you find any errors or omissions, please let us know.

Characteristic

  Canadian Code US code
Tank Construction Designed and fabricated to ASME Section VIII, Div 1, CSA B51 including Annex G

312 psig for internal and 250 psig for external.

Approved design in each jurisdiction.

Includes a corrosion allowance of 25% for externally mounted tanks.

Openings greater than #54 drill shall either be recessed or shall be a “substantial fitting”, equal to least the wall thickness of the vessel

One thousand hour salt spray rating on the coating

Manifold tanks must pass a crush test proving the manifold is capable of withstanding the same crushing load as a single of the same diameter and wall thickness

Liquid withdrawal openings shall be protected with back check valves

Tanks moved from one vehicle to another or being returned to service shall be inspected by an approved organization

Designed and fabricated to ASME Section VIII, Div 1.

External tanks shall be rated for 312 psig if built after 010401, 250 psig if built earlier.

Enclosed tanks shall be rated at 312 psig

Passenger vehicles limited to 200 USG

Non passenger vehicles limited to 300 USG

Tanks larger than 30 USG shall fill into the vapour space

Corrosion resistant coating

If heated, shall be controlled not to exceed 200 psig.

Valves, etc shall be protected from accidental contact.

Tank Installation Tank can not be installed such that the person filling it must lie on the ground

Have a heat shield if closer than 4” from a heat source and not any closer than 8” to the catalytic converter

When installed at the rear of a unibody bus have a reinforced bumper, not be closer than 12” to the rear most point of the bumper and not be closer than 4” to the differential

To have between 7 and 9” road clearance based upon vehicle wheel base if mounted between the axles and 8” if mounted at the rear of the vehicle as well as meeting the clearance angle requirements

The tank shall not project beyond the sides or top of the vehicle

If installed inside a vehicle, to have a rigid, corrosion resistant vapour box, vented to the outside of the vehicle.

The seals for the vapour box rated from -40°C to 35°C, resistant to propane, road salt, vehicle vibration and non swelling or shrinking

Interconnected tanks shall be installed with the tanks level

Located to minimize damage to the container or its fittings

Require a heat shield if located within 18” of a heat source

Nameplate shall be readable directly or with a lamp and mirror

Containers shall not be mounted on the roof, extend beyond the sides of the vehicle, ahead of the front axle or behind the rear axle

Containers mounted between axles shall not extended below the lowest part of the vehicle

Containers mounted behind the axle shall meet the ramp angle also

Shall be mounted to resist vibration

If installed in a vehicle the valves are to be mounted in a gas tight enclosure, vented to the outside

The enclosure, seals, etc shall be of durable materials

General Valve Approved to UL, CSA B12.2 or EN67

Material suitable for service

Melting point greater than 1500°F except for float gauge

Main shut off shall be readily accessible without tools

Relief Valve

Spring loaded internal type

Marked as per code

Directed downward, away from the vehicle, outside of an enclosed space, as far as practical from a source of ignition, protected with a rain cap

Where a pipe-away is used, it shall not restrict the flow of propane, be able to withstand the pressure and be of metallic construction, flexible metallic hose of metal re-enforced hose.

PRV to UL 132 or equal Internal or flush type

Start to leak setting determined by the age of the container

Fusible plugs not allowed

Communicate to vapour space

Marked with code info

Directed upwards or downwards with 45 degrees of vertical

Not impinging on the tank, or vehicle.

If piped away shall have a break away adaptor and no part shall have and ID less than the relief valve opening

The system shall have a length of non-metallic hose installed, as short as possible and capable of withstanding the full pressure from the relief valve.

The system shall be mechanically secured and not routed between the bumper and vehicle

Rain cap on the discharge is required

Fixed Liquid Level Gauge

All tanks to have one c/w# 54 drill opening and to be used to monitor the performance of stop fill valve

The valve shall have a label “If equipped with a stop fill valve, use of fixed liquid level gauge is not required”

All tanks to have one c/w #54 drill opening

Not be used if the tank is equipped with an OPD

Valve is to be labeled with the percentage of the tank it is located for

Double Back Check Valve Permit flow in only one direction Shall operate at stopped or reverse flow
Service Valve Valve to have internal excess flow and automotive closure when engine ignition is off Valve to have manual shut off, excess flow and automotive closure when engine ignition is off
Excess Flow Valve

Engines < or = to 9 l to not exceed 7.6 lpm

Engines > 9 l not to exceed 12.1 lpm

Amendment accepted to change to Engines < or = 240 HP to not exceed 7.6 lpm

Engines > 240 HP not to exceed 12.1 lpm

To close at the flow specified by the manufacturer
Stop Fill Valve To stop flow at 80% of tank capacity and equipped with double back check

Tanks shall be equipped with this and the valve shall have double back check

If the tank is so equipped, a label is placed on the spit valve not requiring its use in low emission transfer stations

Float Gauge As per CSA B51 Annex G Not required
Tank Brackets Design calculations submitted to the jurisdiction for approval confirming the brackets are capable of withstanding 20 G in the forward direction and 8 G in the other two directions, not acting simultaneously

O and J brackets shall have a resilient material installed between the bracket and tank wall

Manufacture to design to 4 G in any direction, not acting simultaneously
Tank Valve Guard Withstand a load of 50 kg dropped from 1.5 m without the tearing out or the shell deforming more than 1t Valves to be protected from damage
Tank Nameplate Mounted such that any corrosion occurring between the tank and nameplate can be monitored. If seal welded, the weld must be checked with LDP or MP Shall be Stainless steel and mounted to minimize corrosion of nameplate and not cause corrosion of the tank
Coating 1000 hr salt spray rating Coated to minimize corrosion
Labels Outlets labels shall be metal or other durable material resistant to water and lettering ¼” high Shall be labeled
Piping A53 or A106 or brass to ASTM B43.

Vapour < 125 psig shall be S40 and if ≥ to 125 psig shall be S80. All liquid piping shall be S80

B36.10M, A 53, A 106B, B 43, or B42

If vapour service is ≤ 125 psig rated at 125,if liquid or vapour > 125 but ≤ to container pressure rated at 250 psig, if > than container pressure, rated at 350 psig, or container pressure, which ever is higher, or 400 psig WOG rating

Exposed pipe shall be of corrosion-resistant material or protected to minimize corrosion

Hose

For vapour service less than 5 psig, hose must be resistant to propane.

All other hose shall be CSA 8.1, CGA Type III with a minimum rated pressure of 350 psig and stainless steel reinforced

The hose shall have flow greater than the excess flow it is connected to.

If used at less than container pressure to be designed and marked for operating pressure
Tube

ASTM A539, SAE J527 or ASTM B75

Minimum thickness based upon diameter

Steel tubing coated with lead and covered in coiled steel wire

Copper tubing to be sheathed in rubber or plastic as per ASTM D572 and marked AUTOPROPANE

Sheath to be cut back 1” at fittings

Fitting shall be rated for the pressure service and accessible

Connections shall be double flare

A 539, B 135, Type L or K of B88, or B280

-if vapour service is ≤ 125 psig rated at 125,if liquid or vapur > 125 but ≤ to container pressure rated at 250 psig, if > than container pressure, rated at 350 psig, or container pressure, which ever is higher, or 400 psig WOG rating

Installer

Shall instruct the user in the safe operation of the system and supply the user with the manufacturers written instructions, where available

Shall be trained

Shall be trained
Fuel Pump Tanks with fuel pumps in them shall be marked as such, equipped with a crash switch and the pump certified to EN67  
Electrical

System shall be separately fused.

Propane-containing components shall not be used to carry electrical current.

Wires shall be protected from damage.

Electrical components contained within propane containing components shall have the propane containing components purged with an inert gas or vacuum purged prior to use

Wiring shall be stranded

All connections water tight and vibration resistant

 
Propane injectors Shall be OEM type and approved to EN67  
Remote Fill Connection Either in a metal enclosure, permanently mounted in the body of the vehicle or located on the bumper such that the vehicle will provide protection  
Bulkhead Fitting Shall be steel or brass with wrench flats on the fitting, have a clamp nut and lockwasher and use a flare, tapered pipe or fitting thread to connect the line  
General

Nested bushing are not allowed

Thread sealant shall be ULC-S642

Bends are not allowed that reduce the cross section area of the part or weaken the part

Close nipples are not allowed

Structural members of the vehicles shall not be cut such that it reduces the vehicle strength

Piping and tubing can not be installed between parts of the vehicle that move relative to one another

Piping and tubing shall be coated on the exterior with a corrosion resistant material

Hose, pipe or tubing shall not be run in concealed areas

If run within 4” of a heat source shall have a heat shield installed

All assembled piping, tubing and hose shall be tested with air or inert gas

All connections on the tank shall be tested with a liquid leak detection solution or device after the equipment is activated

If mono fuel, the gasoline tank and fill connection shall be removed or plugged

Pipe and hose shall be installed to minimize damage and installed in a protected location

If tees are used, the tee shall be in the main fuel line under the floor of the vehicle

When two or more service lines are connected spring-loaded back flow connections shall be used

A hydrostatic relief valve or equal shall be installed between sections of piping, tubing or hose that can be isolated

Vapourizer

Same as converter, or regulator

Sized to suit engine

Securely fastened

Not have a fuse plug

Equipped with a lock off

Approved to EN67

Fabricated from material resistant to propane and were exhaust gases are used to resist the exhaust gas

Rated for at least tank pressure

Not to have a fuse plug

Able to be drained using a valve or plug at the lower end of the unit

To have approved pressure reducing equipment installed between it and the tank

Fuel Lock Off

Connected to ensure only one fuel can be used at one time

Compatible with OEM existing requirements

Located as close to the inlet of gas regulator as possible

Prevent flow of fuel to the carburetor when the engine is not running

Marking All propane vehicles shall be marked with an approved label All propane vehicles shall be marked with an approved label
Re-Inspection All propane vehicles shall have their fuel systems inspected every five years